A50ZSLDR

A50ZSLDR Cofem
Base for A50 algorithmic-addressable detectors with EN 54-23 certified visual alarm  base and EN 54-3 sounder supplied directly from the loop.

There are 2 models available:
• A50ZSLDR: D50 base with sound and light base, addressable.
• A50ZSDDR: D50 base with sound, addressable.

This device needs an addressable detector “with SIRDR functionality” (standard detectors do not have this functionality) which will allow it to operate as a relay associated to this detector. 
Typical uses of the A30XZSDDR and A30XZSLDR are spaces that require integrated fire detection equipment with sounder and visual alarm, such as hotel rooms fitted out for clients with hearing impairments, waiting rooms, nursing rooms, etc.
The coverage of the assembly should not exceed the coverage of the fire detector with which it is installed, unless there is a reason or use that justifies it.

    • Supply: 18-30V with polarity
    • Standby consumption: 0mA
    • Alarm consumption: 19mA / 20mA (Low/High dB)
    • Operative temperature:-10ºC - +55ºC
    • Dimensions: Ø112x43mm (without detector)
    • IP protection: IP21C
    • Sound intensity: Low 90 / High 96 dB - 1m
    • Tones: 31 types
    • Standard: EN 54-3 and 54-23
    • Flash: 0,5Hz (60ms)
    • Κατασκευαστής: Cofem
    • Κωδικός Προϊόντος: A50ZSLDR
    • Διαθεσιμότητα: Διαθέσιμο
    Αναλογική βάση με οπτικό και ηχητικό συναγερμό (για χρήση με ανιχνευτές DR)

    Ετικέτες: A50ZSLDR