SAW-3001
The SAW-3001 addressable sounders are designed for acoustic signaling of fires in a tone manner. They operate on addressable lines/loops of POLON 3000 systems fire alarm control panels. SAW-3001 are activated at the signal sent by the control panel, when the programmed triggering criteria are met, e.g. when a fire is detected in the selected supervisory zone,
The piezoelectric transducer sounder electronics are housed in a frame similar to the Series 40 detector. There is a place to put a 9V 6F22 battery in the case. To mount the siren on the ceiling or wall, use the G-40S socket made of flame retardant plastic – supplied with the siren. There is a screwless terminals connector – placed in the socket – for joining the installation wires The connector has six terminals, two pairs labeled “+” and “-” as the input and output of the detection line and two terminals for connecting an external 24 V power supply.
- Type: tone, acoustic, low current
- Version: addressable
- Mounting: internal
- Supply voltage: 9.6 VDC - 32.0 VDC
- Detection line operating voltage: 16.5 VDC - 24.6 VDC
- External power unit supply voltage: 9.6 VDC - 32 VDC
- Battery current consumption: <150 mA in signaling state
- Current consumption from external power supply: <50 mA in signaling state with 24 VDC power supply
- Current consumption from external power supply: <100 mA in signaling state with 12 VDC power supply
- Sound level: up to 103 dB
- Operating temperature range: -25°C to +55°C
- Frame IP rate: IP 21C
- Dimensions (without socket): Ø115 x 59 mm
- Weight (excluding socket and battery): 0.20 kg
- Other parameters: Operating time from 6LR61 batteries during alarming - min 3h, Surveillance operating time from 6LR61 batteries - from 2 to 5 years