Intelligent Input module for the connection of one conventional detector zone to the Loop
3000 with bidirectional isolator according to EN 54-18. For the connection of conventional
detectors with 12 V or 24 V technology.
- Voltage selection for the detector zone supply via „jumper“ on the module board
- External supply of conventional detector zones for the flexible use of different conventional detectors with different current consumptions and operation voltages
- Possibility for parametrization of short-circuit, wire break, prealarm and alarm thresholds
- Automatic and manual addressing with Loop 3000
- Integrated Isolator and T-branch option
- Functions completely integrated via Loop 3000-protocol
- Multicolour LED for alarm (red) and fault (yellow)
- Aestethical robust wall mounted housing according with IP 54
Technical Data
- Supply Voltage 15 V bis 32 V DC (abs. max. 34 V DC) auf 2-Drahtbus
- Quiescent Current 560 μA
- Alarm Current 560 μA; 5 mA with activated alarm-LED
- Protection class IP 54
- Ambient temperature -10°C to +60°C
- Humidity max. 95%
- Dimensions (H x B x T) 93 mm x 93 mm x 55 mm
- Weight appr. 190 g
- Material ABS, Glass
- Colour Light grey (similar to RAL 7035)
- Standards DIN EN 54-18, EN 54-17
- VDS-approval G 206048
- CE-CPD-Number 0786-CPD-20373
- CE-CPR-Number 0786-CPR-20373