TUN-6046

New Pre-order TUN-6046 Polon Alfa

The TUN-6046 programmable, microprocessor-based, addressable heat detectors is designed to identify fire hazards in rooms where a rapid temperature rise may occur in the first phase of the fire or the temperature may exceed a certain dangerous level. The detector can be programmed from the control panel. Depending from chosen temperature class detector can operate as fixed, rate-of-rase and fixed/rate-of-rase heat detector. It is also possible to change the detector class, adapting it to specific applications. According to the EN 54-5 standard it is possible to choose from A1, A2, B, A2S, BS, A1R, A2R or BR classes.

The detector is designed to identify temperature rise which occurs in the first phase of a fire. It transmits alarm signal to the fire alarm control panel when a threat is identified. Detector can be programmed to operate as fixed, rate-of-rase and fixed/rate-of-rase heat detector.

Compatibility: Detectors operate on addressable lines/loops of POLON 3000/4000/6000 fire alarm control panels.

  • Type: addressable, point
  • Category: Regular working conditions
  • Variety: heat
  • Operational voltage: 16,5 VDC - 24,6 VDC
  • Quiescent current consumption: ≤ 150 µA
  • Detector class: A1, A2, B, A2S, BS, A1R, A2R, BR acc. to PN-EN 54-5
  • Addressing: Automatic address encoding from the control panel
  • Operating temperature range: -25°C to 65°C
  • Relative humidity: up to 95% at 40°C
  • Dimensions of detector with base: Ø115 x 54 mm
  • Weight: 0,2kg
  • Frame colour: white/any colour of the RAL palette (special order only)
  • Brand: POLON-ALFA
  • Product Code: TUN-6046
  • Availability: Pre-order
Addressable universal heat detector