SAB-3006-3RR
Click Image for Gallery
The SAB-3001 addressable sounders are designed for acoustic and optical fire signaling in a tone.. They operate on addressable lines/loops of POLON 3000 fire alarm control panels. Device is activated at the signal sent by the control panel when the programmed triggering criteria are met, e.g. when a fire is detected in the selected supervisory zone.
For proper operation the component requires two supply voltages simultaneously:
- From the detection line
- From an external power supply.
The essential part of the siren is a piezoelectric transducer used to produce an acoustic signal and an LED with a lens located on the top of the siren. The entire unit is mounted in a housing similar to the Series 40 detector. To mount the siren on the ceiling or wall, use the G-40S socket made of flame retardant plastic – supplied with the siren. There is a screwless terminals connector – placed in the socket – for joining the installation wires The connector has six terminals, two pairs labeled “+” and “-” as the input and output of the detection line and two terminals for connecting an external 24 V power supply.
- Type: tone, optical, acustic, low current
- Version: addressable
- Mounting: internal
- Supply voltage: 9,6 VDC - 30.0 VDC
- Detection line operating voltage: 16.5 VDC - 24.6 VDC
- External power unit supply voltage: 9,6 VDC - 30,0 VDC
- Current consumption from external power supply: < 170µA with 24 VDC supply with 24 VDC supply
- Current consumption from external power supply: < 280 mA in signaling mode at 12 VDC supply
- Sound level: up to 103dB
- Flashing frequency: 0,5Hz
- Flash time: 0,2s
- Operating temperature range: -25°C to +55°C
- Frame IP rate: IP 21C
- Dimensions (including socket): Ø115 x 94 mm
- Weight (including socket): 0,26kg