DOT-6046

DOT-6046 Polon Alfa

The DOT-6046 universal smoke and heat detector is designed to identify the initial stage of fire development during which smoke appears with an increase in temperature. It is defined by significant resistance to air movement and pressure changes. Dual smoke detection system (in the IR and UV range) and a dual heat detection system provide an increased immunity to false alarms caused by e.g. water vapour and dust maintaining the small dimensions and high aesthetics of the detector.

The detector is designed to detect the initial stage of fire development, during which smoke appears and/or there is an increase in temperature. It is characterized by significant resistance to the influence of air movement and pressure changes.

Compatibility: Detectors can operate with an addressable lines/loops of POLON 3000/4000/6000 fire alarm control panels only.

  • Type: addressable, point
  • Category: to work in normal conditions
  • Variety: smoke and heat
  • Operational voltage: 16,5 VDC - 24,6 VDC
  • Quiescent current consumption: ≤ 150 µA
  • Detector class: A1R, A1S, BR, BS acc. to PN-EN 54-5
  • Detected test fires: TF1 to TF9
  • Addressing: Automatic address encoding from the control panel
  • Operating temperature range: -25°C to 55°C
  • Relative humidity: up to 95% at 40°C
  • Dimensions of detector with base: Ø115 x 54 mm
  • Weight: 0.18kg
  • Frame colour: white/any colour of the RAL palette (special order only)


  • Brand: POLON-ALFA
  • Product Code: DOT-6046
  • Availability: In Stock
Addressable multisensor, point smoke and temperature detector