PL-3301 O B
Click Image for Gallery
Optical smoke detector for Loop 3000 with 2 optical sensors for earliest fire detection and indication and with bidirectional isolator according to EN 54-7 and EN 54-17
- Exact pollution recognition by an additional independent measuring chamber
- Detector sensitivities automatically calibrated and freely programmable
- Fault monitoring of the measurement chamber signal and Loop 3000-electronics
- Periodic sensor test
- Automatic and manual addressing with Loop 3000
- Integrated Isolator and T-branch option
- Functions completely integrated via Loop 3000-protocol
- Storage of last maintenance date
- Self learning modes for the ambient conditions
- Storage of last maintenance date
- Multicolour LED for alarm (red) and fault (yellow)
Technical Data
- Supply Voltage 15 V to 34 V DC (2-wire bus)
- Quiescent Current 280 μA
- Alarm Current 5 mA
- Output OC: max. 10 mA for parallel indicator or buzzer
- Protection class IP 40
- Ambient temperature -10°C to +60°C
- Humidity max. 95%
- Sensitivity Adjustable in 5 sensitivity levels
- Dimensions (H x D) appr. 47 mm x 110 mm
- Material Metal cover, ABS
- Standards DIN EN 54-7, EN 54-17
- VDS-approval G 205046
- System-approval S 210001, S 216001
- CE-CPD-Number 0786-CPD-20037
- CE-CPR-Number 0786-CPR-20037