Optical smoke detector for conventional systems with an optical measurement method for earliest fire detection and indication according to EN 54-7
- Integrated professional smoke detection system with highest reliability for a secure alarm verification with 16 fold measurement and intelligent logics
- Intelligent analysis and disruption mode for the elimination of false alarms (e.g. cigarette smoke)
- Periodic sensor test
- Integrated Isolator and T-branch option
- LED for alarm (red)
- Integrated locking system for the protection against removal and tamper
- Standard values and application Software version 42 and up please see additional technical table
- Supply Voltage: 9 V to 33 V DC
- Quiescent Current: @ 20 V DC (25°C) 30 µA
- Alarm Current: 20 mA
- Output OC: max. 50 mA for parallel indicator or buzzer
- Ambient Temperature: -10°C to +60°C
- Humidity: max. 95%
- Protection class: IP 40
- Material ABS, Glass
- Colour: White
- Standards: EN 54-7
- VdS-Approval: G 203036
- CE-CPD-Number: 0786-CPD-20042
- Dimensions (H x D): 44 mm x 100 mm
- Response sensitivity: < 0,15 dB/m