808004

808004 Esser
The IQ8Control M as an efficient fire alarm control panel (FACP) for the property supervision of mid-sized to large objects, facilitates simultaneous detection, control and alarm signaling both on the analog ring as well as on the spur.

The loop operation type of the panel (powered-loop or non-powered-loop) can be selected via a jumper located on the power supply card.

Depending on which loop operation type has been selected, the corresponding analog module/modules should be used.

    • Max. five micromodules, with peripheral module Part No. 772477, up to five esserbus loop modules (system supports up to 635 digital loop addresses in total)
    • Max. seven micromodules, with extension module Part No. 772476, up to seven esserbus loop modules (system supports up to 889 digital loop addresses in total)
    • Short circuit and open circuit tolerant loop operation
    • Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
    • Up to 127 esserbus devices (fire detectors and/or manual call points)/detector zones per loop
    • Up to 32 esserbus transponders per loop/operation of wireless components (see chapter 10)
    • Operation types TM and PM as per DIN VDE 0833 - 2 to avoid unwanted alarms being triggered
    • Fire brigade operating panel and transmission interface on the peripheral module
    • Three common relays, freely programmable, monitored, floating for up to 30 V DC/1A (on the peripheral module)
    • TTY or RS 485 or RS 232 interface
    • Integration in the short circuit and open circuit resistant essernet network with up to 31 fire detection panels depends on transmission rate
    • Connection to graphical supervisor WINMAG via serial essernet interface (SEI)
    • Operating panel with alphanumerical display
    • Large display with 8 rows with 40 characters. As follows rated - four rows with 40 characters for the status information (first and last message), and the other four rows with 40 characters are used for system information e.g. “Sounders Off”
    • Event memory for up to 10,000 events
    • All Systems 8000 micromodules are compatible
    • Printer interface for internal printer
    • Two batteries with monitoring circuit
    • Monitored input for external power supply unit


    Additional features for powered loop

    • Max. 6 powered loops and expandable up to 127 loop devices (per loop) in mixed mode / loop powered and non-loop powered (system supports up to 762 digital loop addresses in total)
    • esserbus-PLus (Powered Loop) supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 - 3 with alarm tone as per DIN 33404
    • Up to 48 powered loop base sounders (Series 9200) per loop
    • Up to 32 powered loop IQ8Alarm / IQ8Alarm Plus devices per loop
    • Up to 64 powered loop IQ8Alarm Plus So / FSo devices per loop
    • Up to 48 IQ8Quad with alarm device per loop

    • Brand: ESSER
    • Product Code: 808004
    • Availability: In Stock