CLVR-03XT
The CLVR03XT fire panel haS been designed according to the European standards EN54-2 and EN 54-4 on fire alarm and detection systems, control and indication equipment; EN12094-1 on fixed fire fighting systems and components for gas extinguishing systems.
The CLVR03XT is a combined fire alarm and extinguishing control panels with three independent detection zones.
The control panel is equiped with an integral battery charger and a power supply designed in accordance with EN54-4
Features:
- Independent or combined configuration of the zones
- Configurable sounders delay
- Configurable detection delay
- Option to receive signals from other systems, such as aspiration equipment
- Timer of the remaining time until the release of the extinguishing agent
- Configurable extinguishing delay, up to 60 seconds
- Control of the ventilation/extraction system incorporated
- Supply Voltage: 230VAC
- Supply Fuse: 1.6A
- Battery: 2x12V
- Alarm Current: 0.235A
- Batteries Current: 3A
- Max.Ripple Current: 200milivolts
- Sounder Output: 21 to 28VDC
- Battery Voltage: 27.6VDC
- Dimensions: 385x310x90mm
- Weight: 6kg
- IP Protection: IP30
- Approved and certified according to EN12094-1, EN54-2 and EN54-4